Code Mut 7.003.00076
FLOW SIGNAL PRESSURE
The SFP flow switch closes, or deviates, an electrical contact when the water flow through it reaches the upper calibration value (action), and restores it when it falls below the lower calibration value (release). A pair of permanent magnets in muted repulsion, one inside the body of the flow switch and one exterior, replaces the classic O-ring poststitch solution, allowing a significant increase in reliabilty and flow time.
SFP-S-M2S:
No seat for flow regulator.
Two micro bipolar
Box with IP40 protection
Dn15 Connections (G1 / 2 male threaded connectors "UNI ISO 228)
Operating range: 1.5 l / min ± 0.25
Release rate: = 1.2 l / min
FUNCTIONAL CHARACTERISTICS
- Maximum static pressure: 10 bar
- Maximum fluid temperature: 95 ° C
- Minimum fluid temperature: 5 ° C
- Maximum room temperature: 80 ° C
MATERIALS
- Body: Brass
- Plate: Noryl
- Portamicroswitch box Nylon loaded Glass
- Cover: Brass
- Springs: Stainless Steel
- Cable: H05 VVF